USF Schneider Electric — DC Bus Undervoltage Fault
At a glance
- Severity
- FAULT STOP
- Domain
- DRIVES
- Reference standard
- IEC 61800-5-1
- Product / context
- DC bus undervoltage
What it means
DC bus undervoltage on the drive. The DC bus voltage level has dropped below the minimum allowed threshold. This can be caused by a mains voltage dip, a momentary power interruption, a faulty capacitor precharge circuit, or degraded DC bus capacitors.
Probable causes
- Mains voltage dip or micro-interruption
- DC bus capacitor precharge circuit faulty
- DC bus electrolytic capacitors degraded or dried out
- Three-phase supply with missing or unbalanced phase
Reference values
| undervoltage trip V | {"230V_class":200,"400V_class":370,"690V_class":640} |
|---|---|
| dc bus capacitor check | Measure DC bus discharge time: with drive off, voltage must drop below 50V within < 5 min. If it drops too fast (< 30s), capacitors are degraded. |
Where to start
Does the fault occur at drive power-up or during operation?