F30003 Siemens — DC Bus Undervoltage Fault

At a glance

Severity
FAULT STOP
Domain
DRIVES
Reference standard
IEC 61800-5-1
Product / context
Power unit DC link undervoltage

What it means

DC bus undervoltage on the drive. The DC bus voltage level has dropped below the minimum allowed threshold. This can be caused by a mains voltage dip, a momentary power interruption, a faulty capacitor precharge circuit, or degraded DC bus capacitors.

Probable causes

Reference values

undervoltage trip V{"230V_class":200,"400V_class":370,"690V_class":640}
dc bus capacitor checkMeasure DC bus discharge time: with drive off, voltage must drop below 50V within < 5 min. If it drops too fast (< 30s), capacitors are degraded.

Where to start

Does the fault occur at drive power-up or during operation?

Full guided diagnosis in the app

The diagnostic tree for this fault has 7 guided steps with measurements, checks and resolutions. You'll find it in ElectraIQ, one of the five IndexOS apps: free, works offline.