ObF Schneider Electric — DC Bus Overvoltage Fault
At a glance
- Severity
- FAULT STOP
- Domain
- DRIVES
- Reference standard
- IEC 61800-5-1
- Product / context
- DC bus overvoltage
What it means
DC bus overvoltage on the drive. Typically occurs during deceleration or braking, when the kinetic energy of the load is regenerated back to the drive and the DC bus voltage exceeds the trip threshold. Also frequently caused by excessively high supply voltage.
Probable causes
- Deceleration ramp time too short relative to the load inertia
- Braking resistor missing, faulty, or undersized
- Supply voltage above rated value
- High-inertia load regenerating energy during braking
Reference values
| dc bus nominal V | {"230V_class":325,"400V_class":565,"690V_class":975} |
|---|---|
| overvoltage trip V | {"230V_class":420,"400V_class":810,"690V_class":1200} |
| braking resistor min ohm | {"note":"R_min = Vdc_max^2 / P_brake; typical 30-100 Ohm for 5-30 kW"} |
| braking chopper threshold V | {"230V_class":380,"400V_class":740,"690V_class":1100} |
Where to start
Does the fault occur during motor deceleration/stop or is it present even with the motor at standstill?
Full guided diagnosis in the app
The diagnostic tree for this fault has 9 guided steps with measurements, checks and resolutions. You'll find it in ElectraIQ, one of the five IndexOS apps: free, works offline.