ObF Schneider Electric — DC Bus Overvoltage Fault

At a glance

Severity
FAULT STOP
Domain
DRIVES
Reference standard
IEC 61800-5-1
Product / context
DC bus overvoltage

What it means

DC bus overvoltage on the drive. Typically occurs during deceleration or braking, when the kinetic energy of the load is regenerated back to the drive and the DC bus voltage exceeds the trip threshold. Also frequently caused by excessively high supply voltage.

Probable causes

Reference values

dc bus nominal V{"230V_class":325,"400V_class":565,"690V_class":975}
overvoltage trip V{"230V_class":420,"400V_class":810,"690V_class":1200}
braking resistor min ohm{"note":"R_min = Vdc_max^2 / P_brake; typical 30-100 Ohm for 5-30 kW"}
braking chopper threshold V{"230V_class":380,"400V_class":740,"690V_class":1100}

Where to start

Does the fault occur during motor deceleration/stop or is it present even with the motor at standstill?