DM-1001 SMA — RS485 Communication Failure
At a glance
- Severity
- WARNING
- Domain
- MONITORING_COMM
- Reference standard
- EIA/TIA-485 / Modbus RTU
- Product / context
- Device Communication Error (RS485)
What it means
Fault on the RS485/Modbus RTU serial communication between the datalogger and field devices (inverters, meters, sensors). One or more devices are not communicating.
Probable causes
- A/B wire polarity reversed on one or more bus nodes.
- 120 ohm termination resistor missing or incorrectly positioned.
- Baud rate or serial parameters (parity, stop bit) not uniform across devices.
- Modbus address conflict: two devices with the same slave ID.
Reference values
| RS485 | {"termination":"120 Ω at the two bus ends only","polarity":"A/B (D+, D−)","max_nodes":"32 per segment","typical_baud":"9600-115200","nota":"Replace the cable with shielded twisted pair in noisy environments."} |
|---|
Where to start
Check the RS485 wiring: verify the A(+) and B(-) wire polarity on every device, cable continuity, and shield grounded at one point only. Is the wiring correct?