FAL 01 Omron — Memory error / backup battery depleted
At a glance
- Severity
- WARNING
- Domain
- PLC
- Reference standard
- IEC 61131-2
- Product / context
- Memory error / backup battery low — CP1/CJ2
What it means
The CPU reports a retentive memory or backup battery error. On battery-equipped CPUs (older series), the BAT/BATF LED is flashing or solid. On newer CPUs with flash memory, the error indicates non-volatile memory corruption. Retentive data (counters, recipes, operating hours) are at risk of being lost at the next power-off.
Probable causes
- Lithium backup battery exhausted after 5-10 years of service.
- Memory card with damaged sectors or corrupted by power interruption during write.
- Excessive write cycles on flash memory (intensive data logging on memory card).
- Ambient temperature out of range reducing battery and memory life.
Where to start
Does the CPU have a BAT/BATF LED lit or flashing? (Note: Siemens S7-1500 CPUs and recent CPUs do not use batteries -- skip to the next step if not applicable.)
Full guided diagnosis in the app
The diagnostic tree for this fault has 7 guided steps with measurements, checks and resolutions. You'll find it in ElectraIQ, one of the five IndexOS apps: free, works offline.
Printable sheet + Omron updates
Leave your email: get the link to the printable Omron error-code sheet and a heads-up when we add new codes and guides.
Double opt-in, zero spam, one-click unsubscribe.
The same fault on other brands
- Minor Fault Type 10 Allen-Bradley
- 1610 Mitsubishi Electric
- Battery Fault (ERR LED) Schneider Electric
- W#16#35A3 Siemens
More Omron codes
- 24VDC Dropout — Unstable PLC power supply — cyclic restarts
- ERR 0x0084 — Analog input module — full-scale reading or error
- ERR 0x0401 — Digital input module — input not reading (stuck at 0)
- FAL 80 — Digital output module — output not activating
- FAL 9F — CPU ↔ I/O module communication error (backplane bus)
- Safety Input Passivated — Safety module F-CPU/F-DI/F-DO in passivation
- FAL C0 — PLC Communication Fault / Network Timeout