24VDC Dropout Omron — Unstable PLC power supply — cyclic restarts
At a glance
- Severity
- FAULT STOP
- Domain
- PLC
- Reference standard
- IEC 61131-2
- Product / context
- Unstable 24VDC supply / cyclic reset
What it means
The PLC restarts cyclically (power cycling) or has intermittent interruptions. CPU LEDs turn off and back on in the boot sequence. The program is interrupted causing unpredictable machine stops. Actuators may behave erratically during restart phases.
Probable causes
- 24VDC power supply undersized or failing (voltage drops below threshold during peak loads).
- Loose or oxidized power terminals causing micro-interruptions.
- Disturbances on the upstream 230VAC mains (voltage spikes, mains micro-interruptions).
- Intermittent short circuit on the 24VDC line causing the power supply voltage to drop.
Reference values
| alimentazione 24VDC | {"nominale":24,"acceptable_range":"20.4-28.8 V","ripple":"< 5%","nota":"Also check the protective fuses on the modules."} |
|---|
Where to start
Measure with a multimeter the 24VDC voltage directly at the CPU power terminals. Is the value stable between 23.5V and 25.5V under load?
Full guided diagnosis in the app
The diagnostic tree for this fault has 7 guided steps with measurements, checks and resolutions. You'll find it in ElectraIQ, one of the five IndexOS apps: free, works offline.
Printable sheet + Omron updates
Leave your email: get the link to the printable Omron error-code sheet and a heads-up when we add new codes and guides.
Double opt-in, zero spam, one-click unsubscribe.
The same fault on other brands
- Major Fault Type 1 (Power-up) Allen-Bradley
- PWR LED Orange/Off Schneider Electric
- 16#0001 / Power Dropout Siemens
More Omron codes
- ERR 0x0084 — Analog input module — full-scale reading or error
- ERR 0x0401 — Digital input module — input not reading (stuck at 0)
- FAL 01 — Memory error / backup battery depleted
- FAL 80 — Digital output module — output not activating
- FAL 9F — CPU ↔ I/O module communication error (backplane bus)
- Safety Input Passivated — Safety module F-CPU/F-DI/F-DO in passivation
- FAL C0 — PLC Communication Fault / Network Timeout