ERR 0x0401 Omron — Digital input module — input not reading (stuck at 0)
At a glance
- Severity
- DEGRADED
- Domain
- PLC
- Reference standard
- IEC 61131-2
- Product / context
- I/O input module verification/status error
What it means
A digital input channel on the PLC remains stuck at 0 (FALSE) despite the field sensor or contact being active. The channel status LED on the module does not light up. The problem may be in the wiring, the sensor, or the module itself.
Probable causes
- Broken cable or loose terminal on the module terminal strip.
- Faulty sensor or missing sensor supply (PNP/NPN without 24V).
- Module channel burned out due to overvoltage or short circuit.
- Incorrect input address in the PLC program (variable mapped to the wrong channel).
Where to start
Using a multimeter, measure the voltage between the input terminal in question and the common (0V/M) directly on the module terminal strip. Do you read 24VDC when the sensor is activated?
Full guided diagnosis in the app
The diagnostic tree for this fault has 7 guided steps with measurements, checks and resolutions. You'll find it in ElectraIQ, one of the five IndexOS apps: free, works offline.
Printable sheet + Omron updates
Leave your email: get the link to the printable Omron error-code sheet and a heads-up when we add new codes and guides.
Double opt-in, zero spam, one-click unsubscribe.
The same fault on other brands
More Omron codes
- 24VDC Dropout — Unstable PLC power supply — cyclic restarts
- ERR 0x0084 — Analog input module — full-scale reading or error
- FAL 01 — Memory error / backup battery depleted
- FAL 80 — Digital output module — output not activating
- FAL 9F — CPU ↔ I/O module communication error (backplane bus)
- Safety Input Passivated — Safety module F-CPU/F-DI/F-DO in passivation
- FAL C0 — PLC Communication Fault / Network Timeout