1610 Mitsubishi Electric — Memory error / backup battery depleted
At a glance
- Severity
- WARNING
- Domain
- PLC
- Reference standard
- IEC 61131-2
- Product / context
- Low battery voltage — FX5U
What it means
The CPU reports a retentive memory or backup battery error. On battery-equipped CPUs (older series), the BAT/BATF LED is flashing or solid. On newer CPUs with flash memory, the error indicates non-volatile memory corruption. Retentive data (counters, recipes, operating hours) are at risk of being lost at the next power-off.
Probable causes
- Lithium backup battery exhausted after 5-10 years of service.
- Memory card with damaged sectors or corrupted by power interruption during write.
- Excessive write cycles on flash memory (intensive data logging on memory card).
- Ambient temperature out of range reducing battery and memory life.
Where to start
Does the CPU have a BAT/BATF LED lit or flashing? (Note: Siemens S7-1500 CPUs and recent CPUs do not use batteries -- skip to the next step if not applicable.)
Full guided diagnosis in the app
The diagnostic tree for this fault has 7 guided steps with measurements, checks and resolutions. You'll find it in ElectraIQ, one of the five IndexOS apps: free, works offline.
Printable sheet + Mitsubishi Electric updates
Leave your email: get the link to the printable Mitsubishi Electric error-code sheet and a heads-up when we add new codes and guides.
Double opt-in, zero spam, one-click unsubscribe.
The same fault on other brands
- Minor Fault Type 10 Allen-Bradley
- FAL 01 Omron
- Battery Fault (ERR LED) Schneider Electric
- W#16#35A3 Siemens
More Mitsubishi Electric codes
- 3100 — Digital output module — output not activating
- 1102 — Discharge Temperature Too High
- 1102 — Capacity unbalance between circuits
- 1300 — Low Pressure Alarm / Refrigerant Shortage
- 1300 — Low Pressure Alarm / LP Lockout
- 1302 — High Pressure Alarm / HP Lockout
- 1302 — Sub-cooling fault / abnormal sub-cooling
- 4250 — Compressor Fault / Overcurrent Protection