4250 Mitsubishi Electric — Compressor Fault / Overcurrent Protection
At a glance
- Severity
- FAULT STOP
- Domain
- HEAT_PUMP_SYSTEM
- Reference standard
- EN 60335-2-40 / IEC 60335-2-40
What it means
Compressor overcurrent protection tripped.
Probable causes
- Scroll compressor mechanically seized
- Windings with partial short circuit
- Inverter module faulty
- Persistent high condensing pressure
- Supply voltage unstable or unbalanced
Where to start
Measure winding insulation to ground (>1 MOhm). Is it sufficient?
Full guided diagnosis in the app
The diagnostic tree for this fault has 5 guided steps with measurements, checks and resolutions. You'll find it in HVACIQ, one of the five IndexOS apps: free, works offline.
Printable sheet + Mitsubishi Electric updates
Leave your email: get the link to the printable Mitsubishi Electric error-code sheet and a heads-up when we add new codes and guides.