BATTERY FAULT Eaton — Replace Battery / Battery Fault
At a glance
- Severity
- WARNING
- Domain
- UPS_SYSTEM
- Reference standard
- IEC 62040-1 / EN 50600-2-2
What it means
The battery test fails or the string cannot hold the load: degraded VRLA blocks, high temperature or insufficient charging. Actual runtime is shorter than rated.
Probable causes
- Natural end of life of VRLA batteries (3-5 years at 20-25 C)
- Degraded block or element in the string
- High ambient temperature shortening life and capacity
- Charger float voltage out of calibration
- Sulfation after long periods without charge
Where to start
Start the automatic battery test from the panel and read the string voltage at rest and under load.
Full guided diagnosis in the app
The diagnostic tree for this fault has 5 guided steps with measurements, checks and resolutions. You'll find it in DataCIQ, one of the five IndexOS apps: free, works offline.
Printable sheet + Eaton updates
Leave your email: get the link to the printable Eaton error-code sheet and a heads-up when we add new codes and guides.