JOINT OVERHEAT ABB — Busway / Tap-off Overheat
At a glance
- Severity
- WARNING THEN STOP
- Domain
- TRANSFER_SWITCH_SYSTEM
- Reference standard
- IEC 61439-6
What it means
Overheated busway joints or tap-offs: busbar distribution outage and fire risk above the racks.
Probable causes
- Joints not torqued or removed and refitted badly
- Tap-offs overloaded or poorly seated
- Load imbalance across busway phases
- Dust accumulated in joints
Where to start
Thermography of the busway route under load: compare joints and tap-offs with peers.