2330 ABB — Ground Fault

At a glance

Severity
FAULT STOP
Domain
DRIVES
Reference standard
IEC 61800-5-1
Product / context
Earth leakage

What it means

Ground fault detected on the drive output side (motor cable or motor windings). The drive has detected a leakage current to ground exceeding the configured threshold. This type of fault is hazardous to both personnel and the drive and requires immediate intervention.

Probable causes

Where to start

Disconnect the motor cable from the drive terminals (U/V/W). Measure the insulation of each phase to ground (PE) with a 500V DC megger. Are the values above 1 MΩ?