FEED MISMATCH ABB — Wrong A/B Feed Assignment
At a glance
- Severity
- WARNING
- Domain
- TRANSFER_SWITCH_SYSTEM
- Reference standard
- EN 50600-2-2
What it means
Dual-PSU equipment fed from the same chain (or same PDU): the 2N redundancy is lost in the last stretch and a single fault drops the load.
Probable causes
- Later installations ignoring the A/B map
- PDU A and B connected to the same floor board
- Missing or wrong plug labelling
- Load growth never audited
Where to start
Sample or full audit: for every dual-PSU device verify the two plugs land on two different PDUs, themselves on two different chains.
Full guided diagnosis in the app
The diagnostic tree for this fault has 3 guided steps with measurements, checks and resolutions. You'll find it in DataCIQ, one of the five IndexOS apps: free, works offline.
Printable sheet + ABB updates
Leave your email: get the link to the printable ABB error-code sheet and a heads-up when we add new codes and guides.
Double opt-in, zero spam, one-click unsubscribe.
The same fault on other brands
More ABB codes
- JOINT OVERHEAT — Busway / Tap-off Overheat
- STS FAULT — STS Transfer Failure
- TRANSFER FAULT — ATS Transfer Failure
- 2310 — Overcurrent Fault
- 2330 — Ground Fault
- 3210 — DC Bus Overvoltage Fault
- 3220 — DC Bus Undervoltage Fault
- 4310 — Drive Overtemperature Fault