LEAK DETECTED Vertiv — Water Leak / Condensate Overflow
At a glance
- Severity
- FAULT STOP
- Domain
- PRECISION_COOLING_SYSTEM
- Reference standard
- EN 50600-3-1 / EN 378
What it means
The leak detection system trips: water in the condensate tray, a clogged drain or a leak from the humidifier group. Many units stop for safety.
Probable causes
- Condensate drain tube clogged or dry trap
- Condensate pump failed (where present)
- Leak from the humidifier group or water valves
- Leak detection sensor wet, dirty or out of position
- Iced evaporator coil overflowing during defrost
Where to start
Localize: inspect the condensate tray, drain tube and trap, humidifier group and leak sensor placement.
Full guided diagnosis in the app
The diagnostic tree for this fault has 4 guided steps with measurements, checks and resolutions. You'll find it in DataCIQ, one of the five IndexOS apps: free, works offline.