HIGH HEAD PRESSURE Vertiv — High Head Pressure Alarm
At a glance
- Severity
- FAULT STOP
- Domain
- PRECISION_COOLING_SYSTEM
- Reference standard
- EN 378 / F-Gas EU 517/2014
What it means
Condensing pressure exceeds the limit and the CRAC compressor stops: the room is no longer cooled.
Probable causes
- Dirty condenser coil (dust, fibres, salt)
- Condenser fans failed or running slow
- Refrigerant overcharge or non-condensables in the circuit
- Outdoor temperature above design conditions
- Head pressure control (modulating fans) out of calibration
Where to start
Measure condensing pressure and subcooling against the P/T chart of the refrigerant at the current outdoor temperature.
Full guided diagnosis in the app
The diagnostic tree for this fault has 5 guided steps with measurements, checks and resolutions. You'll find it in DataCIQ, one of the five IndexOS apps: free, works offline.