W#16#75D1 Siemens — Safety module F-CPU/F-DI/F-DO in passivation
At a glance
- Severity
- FAULT STOP
- Domain
- PLC
- Reference standard
- IEC 62061 / IEC 61508 SIL3
- Product / context
- F-Module passivated — S7-1500F PROFIsafe
What it means
A safety module (F-module) has entered passivation state: the safety I/O values are replaced with safe values (typically 0). This occurs when the safety system detects an inconsistency between redundant channels, a PROFIsafe communication error, or a hardware fault in the F-module. The machine stops because safety consents are removed.
Probable causes
- Discrepancy between the two redundant channels of a safety input (e.g., only one E-Stop contact opened).
- PROFIsafe communication error: timeout, CRC error, or duplicate F-address on the network.
- Incorrect wiring on F-DI inputs: test pulse sensor not connected or incorrectly connected.
- Safety parameters (F-Address, F-WD Time) inconsistent between the configuration and the physical module.
Where to start
Identify the passivated F-module from the online diagnostics (in TIA Portal: Safety Administration, in Studio 5000: Safety Task Faults). Does the module report a PROFIsafe/CIP Safety communication error?
Full guided diagnosis in the app
The diagnostic tree for this fault has 7 guided steps with measurements, checks and resolutions. You'll find it in ElectraIQ, one of the five IndexOS apps: free, works offline.
Printable sheet + Siemens updates
Leave your email: get the link to the printable Siemens error-code sheet and a heads-up when we add new codes and guides.
Double opt-in, zero spam, one-click unsubscribe.
The same fault on other brands
- Safety Task Fault Type 14 Allen-Bradley
- Safety Input Passivated Omron
- SIL3 Safety Fault Schneider Electric
More Siemens codes
- 16#0001 / Power Dropout — Unstable PLC power supply — cyclic restarts
- 16#0006 (OB82 DI) — Digital input module — input not reading (stuck at 0)
- 32767 / -32768 (Overflow/Underflow) — Analog input module — full-scale reading or error
- Short-circuit / L+ Missing (DQ) — Digital output module — output not activating
- W#16#0049 — CPU in STOP
- W#16#35A3 — Memory error / backup battery depleted
- W#16#38AA — CPU ↔ I/O module communication error (backplane bus)
- 0xE900 / 0xE901 — IO-Link communication lost (device not responding)