CH45 LG — Outdoor Coil Sensor Fault / Evaporator Temperature Error
At a glance
- Severity
- WARNING THEN STOP
- Domain
- HEAT_PUMP_SYSTEM
- Reference standard
- EN 14511 / EN 60335-2-40
- Product / context
- Condenser coil thermistor fault
What it means
Outdoor coil temperature sensor faulty or out of range.
Probable causes
- Outdoor coil NTC sensor faulty or disconnected
- Sensor connector oxidized or loose
- Broken cable between sensor and board
- Electronic board not reading the signal correctly
Reference values
| NTC 10k 25C resistenza kohm | {"-10C":"55.3","0C":"32.6","10C":"19.9","20C":"12.5","25C":"10.0","30C":"8.06","40C":"5.32","60C":"2.49"} |
|---|---|
| nota | Typical 10 kΩ B3950 NTC table: always compare with the manufacturer table. |
Where to start
Measure the outdoor coil NTC sensor resistance. Is the value consistent with ambient temperature?
Full guided diagnosis in the app
The diagnostic tree for this fault has 5 guided steps with measurements, checks and resolutions. You'll find it in HVACIQ, one of the five IndexOS apps: free, works offline.
Printable sheet + LG updates
Leave your email: get the link to the printable LG error-code sheet and a heads-up when we add new codes and guides.
Double opt-in, zero spam, one-click unsubscribe.
The same fault on other brands
More LG codes
- CH35 — Low Pressure Alarm / Refrigerant Shortage
- CH01 — Room Temperature Sensor Fault
- CH05 — Indoor Unit Communication Error
- CH05 — Refrigerant addressing error
- CH22 — Compressor Overcurrent / Overload Protection
- CH32 — Discharge Temperature Too High
- CH32 — Capacity unbalance between circuits
- CH34 — High Pressure Alarm / HP Lockout