CH45 LG — Outdoor Coil Sensor Fault / Evaporator Temperature Error

At a glance

Severity
WARNING THEN STOP
Domain
HEAT_PUMP_SYSTEM
Reference standard
EN 14511 / EN 60335-2-40
Product / context
Condenser coil thermistor fault

What it means

Outdoor coil temperature sensor faulty or out of range.

Probable causes

Reference values

NTC 10k 25C resistenza kohm{"-10C":"55.3","0C":"32.6","10C":"19.9","20C":"12.5","25C":"10.0","30C":"8.06","40C":"5.32","60C":"2.49"}
notaTypical 10 kΩ B3950 NTC table: always compare with the manufacturer table.

Where to start

Measure the outdoor coil NTC sensor resistance. Is the value consistent with ambient temperature?