CH32 LG — Capacity unbalance between circuits
At a glance
- Severity
- WARNING
- Domain
- VRV_VRF_system
- Reference standard
- EN 14511, ASHRAE 90.1
- Product / context
- Discharge temperature too high
What it means
The VRV/VRF system shows a significant capacity imbalance between different circuits or branches. Some indoor units reach the setpoint while others remain far from it. The system cannot balance the thermal load between compressors, causing inefficient operation and reduced comfort.
Probable causes
- Very different piping lengths between system branches
- Incorrect sizing of indoor units relative to the thermal load
- EEVs of some indoor units with incorrect opening or stuck
- Branch controller with partially obstructed valves
- Very dirty air filters on some indoor units reducing capacity
Where to start
Is the imbalance between units on the same branch or on different branches?
Full guided diagnosis in the app
The diagnostic tree for this fault has 5 guided steps with measurements, checks and resolutions. You'll find it in HVACIQ, one of the five IndexOS apps: free, works offline.
Printable sheet + LG updates
Leave your email: get the link to the printable LG error-code sheet and a heads-up when we add new codes and guides.
Double opt-in, zero spam, one-click unsubscribe.
The same fault on other brands
More LG codes
- CH05 — Refrigerant addressing error
- CH34 — Sub-cooling fault / abnormal sub-cooling
- CH01 — Room Temperature Sensor Fault
- CH05 — Indoor Unit Communication Error
- CH22 — Compressor Overcurrent / Overload Protection
- CH32 — Discharge Temperature Too High
- CH34 — High Pressure Alarm / HP Lockout
- CH35 — Low Pressure Alarm / Refrigerant Shortage