String Reverse Connection Huawei — Reverse Polarity
At a glance
- Severity
- FAULT STOP
- Domain
- DC_SIDE
- Reference standard
- IEC 62548 / CEI 64-8 Sez. 712
- Product / context
- String reverse connection
What it means
A string is connected with reversed polarity to the inverter input, or a single module in the string is wired with swapped cables. The inverter detects negative voltage on the DC input and shuts down for protection.
Probable causes
- Wiring error during installation: positive cable connected to the negative terminal of the inverter.
- Single module in the string with swapped MC4 connectors (+ and - reversed).
- Incorrect cable labeling of string cables in the combiner box.
- Replacement of a module with reversed connection relative to the chain.
Where to start
WARNING: do not attempt to disconnect MC4 connectors under load with reversed polarity (arc risk). Open the DC disconnector first. Measure the voltage at the inverter DC terminals with a multimeter. Is the voltage negative?
Full guided diagnosis in the app
The diagnostic tree for this fault has 6 guided steps with measurements, checks and resolutions. You'll find it in ElectraIQ, one of the five IndexOS apps: free, works offline.
Printable sheet + Huawei updates
Leave your email: get the link to the printable Huawei error-code sheet and a heads-up when we add new codes and guides.
Double opt-in, zero spam, one-click unsubscribe.
The same fault on other brands
More Huawei codes
- DC Arc Fault — DC Arc Fault Circuit Interruption (AFCI)
- FusionSolar - Data Gap Alert — Remote Monitoring Platform Sync
- Grid Failure — Grid Fault — Frequency/Voltage Out of Range
- Grid Protection Trip — CEI 0-21 Interface Protection
- Low Insulation Resistance — Ground Fault (GFDI / IMD)
- N/A — Inverter Replacement Commissioning
- Overtemperature — Thermal Derating
- SmartLogger - EMI Sensor Error — Environmental Sensor Fault