A5 Daikin — Filter pressure drop high

At a glance

Severity
WARNING
Domain
air_handling_unit
Reference standard
EN ISO 16890, UNI 10339, ASHRAE 52.2
Product / context
Freeze-up protection (reduced airflow)

What it means

The pressure drop across the AHU filters exceeds the set limit value. The filters are clogged and reduce airflow, compromising indoor air quality and energy efficiency. If not addressed, the fan operates under overload and indoor comfort deteriorates.

Probable causes

Reference values

filter pressure drop pa{"new":"50-120","replacement":"> 250 (indicative, depends on filter class)","nota":"Compare with the commissioning value at nominal airflow."}

Where to start

Replace the filters immediately. Use filters of the same class and size. Check filter frame gaskets to prevent bypass. Reset the alarm after replacement. Record the date for the next service interval.