A5 Daikin — Damper actuator stuck
At a glance
- Severity
- WARNING
- Domain
- air_handling_unit
- Reference standard
- UNI EN 13053, UNI EN 1751, ASHRAE 90.1
- Product / context
- Freeze-up protection
What it means
An AHU damper actuator (outdoor air, recirculation air, mixing, or free-cooling damper) is stuck in one position and does not respond to the command. This compromises airflow control and thermo-hygrometric conditions. If the outdoor air damper is stuck open in winter, there is a risk of coil freezing.
Probable causes
- Electric actuator with burned motor or broken gears
- Damper mechanically stuck due to corrosion or debris
- Actuator wiring broken or connector disconnected
- Command signal from controller absent
- Actuator return spring broken (for spring-return actuators)
Where to start
Check the damper position visually. Try to move it manually (with actuator disconnected). If mechanically stuck, look for corrosion or debris. If it moves freely, the problem is in the actuator.