TOWER APPROACH HIGH Trane — Cooling Tower / Dry Cooler Degradation
At a glance
- Severity
- WARNING THEN STOP
- Domain
- CHILLED_WATER_SYSTEM
- Reference standard
- EN 378 / legionella guidelines
What it means
Degraded towers or dry coolers (scale, algae, fans): heat is not rejected, condensing worsens until chillers trip.
Probable causes
- Dirty or scaled fill and coils
- Inadequate water treatment (towers: legionella risk too)
- Fans failed or running slow
- Blowdown and make-up not calibrated
Where to start
Compare tower/dry cooler approach with baseline and inspect fill, fans and water quality.