AL28 Trane — Coil freeze protection
At a glance
- Severity
- FAULT STOP
- Domain
- air_handling_unit
- Reference standard
- UNI EN 13053, EN 378, ASHRAE 90.1
- Product / context
- Coil freeze protection
What it means
The AHU anti-freeze thermostat has tripped, indicating that the air temperature downstream of the heating/cooling coil has dropped below the safety threshold (typically +5 degrees C). This protects the water coil from freezing, which would cause pipe rupture with water leakage and major damage.
Probable causes
- Outdoor air damper stuck open with outdoor temperatures below zero
- Hot water coil not supplied (pump stopped, valve closed)
- 3-way valve of the hot coil stuck in closed position
- Anti-freeze thermostat defective or poorly positioned
- Glycol absent or at insufficient concentration in the water circuit
- Power supply interruption during winter
Where to start
The capillary anti-freeze thermostat has tripped. What is the outdoor temperature?
Full guided diagnosis in the app
The diagnostic tree for this fault has 5 guided steps with measurements, checks and resolutions. You'll find it in HVACIQ, one of the five IndexOS apps: free, works offline.
Printable sheet + Trane updates
Leave your email: get the link to the printable Trane error-code sheet and a heads-up when we add new codes and guides.
Double opt-in, zero spam, one-click unsubscribe.
The same fault on other brands
More Trane codes
- AL06 — Belt broken or slipping
- AL55 — Humidifier fault
- AL01 — High Pressure Cutout / HP Alarm
- AL02 — Low Pressure Cutout / LP Alarm
- AL21 — Water Flow Switch Alarm / No Flow
- AL28 — Anti-Freeze Protection / Evaporator Freeze Risk
- AL42 — Oil Pressure Differential Fault
- AL42 — Oil recovery failure / compressor oil not returning