039 Sungrow — Low Insulation Resistance (Riso Low)
At a glance
- Severity
- FAULT STOP
- Domain
- DC_SIDE
- Reference standard
- IEC 62446-1
- Product / context
- Low System Insulation Resistance
What it means
The inverter detects an insulation resistance to ground on the DC side below the safety threshold (e.g. < 1 MΩ).
Probable causes
- Water ingress into MC4 connectors.
- Solar cables mechanically damaged or crushed against mounting structures.
- Moisture penetration into PV modules (PID).
Reference values
| pv insulation | {"test":"1000 VDC (EN 62446-1)","system_minimum":"≥ 1 MΩ","healthy_string_typical":"> 40 MΩ","nota":"Measure per polarity and per string, inverter disconnected."} |
|---|
Where to start
Turn off the inverter (AC side) and open all DC disconnectors. Is the fault still displayed?
Full guided diagnosis in the app