F270 / F437 Endress+Hauser — 4-20mA signal out of range (below 3.8mA or above 20.5mA)

At a glance

Severity
FAULT STOP
Domain
INSTRUMENTATION
Reference standard
NAMUR NE 43 / IEC 60770
Product / context
Current output failure — Proline / Cerabar

What it means

The 4-20mA analog transmitter is providing a signal outside the NAMUR NE 43 limits: current below 3.8mA (low fault indication) or above 20.5mA (high fault indication or saturation). The PLC or control system detects the value as out of range and triggers a diagnostic alarm. The associated process measurement is unreliable.

Probable causes

Reference values

loop 4 20mA{"live_zero":"4 mA = 0% of span","broken_wire":"< 3.6 mA","overrange":"> 21 mA","supply":"24 VDC ±10%","max_loop_resistance":"≈ 600 Ω with 12 V at the transmitter"}

Where to start

Measure the loop current with a multimeter in series (or use the PLC mA function if available). Is the reading 0mA or very close to zero?

Full guided diagnosis in the app

The diagnostic tree for this fault has 9 guided steps with measurements, checks and resolutions. You'll find it in ElectraIQ, one of the four IndexOS apps: free, works offline.