OverRange / UnderRange (AI) Allen-Bradley — Analog input module — full-scale reading or error
At a glance
- Severity
- WARNING
- Domain
- PLC
- Reference standard
- IEC 61131-2
- Product / context
- Full-scale overflow or open 4-20mA loop
What it means
An analog channel on the PLC reads a full-scale value (e.g., 32767 or 27648 for Siemens, i.e., > 20mA / > 10V) or an underflow/overflow value. This typically indicates a problem with the 4-20mA transmitter wiring or the temperature sensor (PT100, thermocouple).
Probable causes
- Transmitter cable broken (4-20mA loop open -- reads 0mA or overflow).
- Transmitter not powered or faulty.
- Channel configuration incorrect (range, measurement type, resolution) in the PLC software.
- Analog cable shielding not connected or connected on both sides (EMC interference).
Where to start
Check the module diagnostics to determine if the channel is in overflow (value > full scale) or underflow (value < range start, e.g., < 4mA). What is the condition?
Full guided diagnosis in the app
The diagnostic tree for this fault has 7 guided steps with measurements, checks and resolutions. You'll find it in ElectraIQ, one of the five IndexOS apps: free, works offline.
Printable sheet + Allen-Bradley updates
Leave your email: get the link to the printable Allen-Bradley error-code sheet and a heads-up when we add new codes and guides.
Double opt-in, zero spam, one-click unsubscribe.
The same fault on other brands
More Allen-Bradley codes
- I/O Channel Fault (DI) — Digital input module — input not reading (stuck at 0)
- Major Fault Type 1 — CPU in STOP
- Major Fault Type 1 (Power-up) — Unstable PLC power supply — cyclic restarts
- Major Fault Type 3 — CPU ↔ I/O module communication error (backplane bus)
- Minor Fault Type 10 — Memory error / backup battery depleted
- Safety Task Fault Type 14 — Safety module F-CPU/F-DI/F-DO in passivation
- 16#0204 — PLC Communication Fault / Network Timeout