050 Sungrow — CEI 0-21 Interface Protection

At a glance

Severity
FAULT STOP
Domain
MONITORING_COMM
Reference standard
CEI 0-21 (Ed. 2019) / Allegato A70
Product / context
Grid Protection Parameter Error

What it means

Verification and maintenance of interface protections according to the CEI 0-21 standard for LV-connected systems. Checking the protection relay trip thresholds (59.S1, 27.S1, 81>.S1, 81<.S1) and trip times.

Probable causes

Where to start

Access the interface protection relay (SPI) and read the currently set thresholds. Compare the values with the CEI 0-21 table (59.S1 = 1.10 Vn, 27.S1 = 0.85 Vn, 81>.S1 = 50.3 Hz, 81<.S1 = 49.7 Hz). Are the values compliant?

Full guided diagnosis in the app

The diagnostic tree for this fault has 7 guided steps with measurements, checks and resolutions. You'll find it in ElectraIQ, one of the four IndexOS apps: free, works offline.

Download on the App Store Get it on Google Play

Open ElectraIQ

Printable sheet + Sungrow updates

Leave your email: get the link to the printable Sungrow error-code sheet and a heads-up when we add new codes and guides.

Double opt-in, zero spam, one-click unsubscribe.

The same fault on other brands