VALVE FAULT Siemens — Control Valve Stuck
At a glance
- Severity
- WARNING THEN STOP
- Domain
- CHILLED_WATER_SYSTEM
- Reference standard
- EN 50600-3-1
What it means
Control valve stuck or actuator failed: flow imbalance across zones, room units out of thermal control.
Probable causes
- Deposits and scale on the plug
- Actuator or positioner failed
- Command signal missing (controller, BMS)
- Stroke not calibrated after maintenance
Where to start
Verify commanded vs actual valve position and the command signal (0-10 V / 4-20 mA) from the controller.