Bus KNX interrotto Siemens — KNX/DALI Bus Fault / Communication Error
At a glance
- Severity
- FAULT STOP
- Domain
- LIGHTING_AUTOMATION
- Reference standard
- IEC 62386 / EN 15193
- Product / context
- KNX bus power or communication interrupted
What it means
The communication bus (KNX or DALI) has a fault. Luminaires or devices do not respond to commands, remain in their previous state, or turn off. The controller reports devices offline or bus communication errors.
Probable causes
- Short circuit on the DALI bus (damaged cable insulation)
- DALI power supply faulty (bus voltage must be 11.5-20.5V)
- Too many devices on the bus (maximum 64 per DALI line)
- Duplicate DALI address after driver replacement
- DALI wiring with excessive length (max 300m with 1.5mm2 cross-section)
- KNX bus power supply faulty or overloaded (bus voltage 21-30V DC)
- Duplicate KNX individual address after device replacement
- Short circuit or break on the KNX bus line (check line/area topology)
Reference values
| DALI | {"bus":"16 V nominal (9.5-22.5 V)","max_psu":"250 mA","addresses":"64 devices + 16 groups"} |
|---|---|
| KNX TP1 | {"bus":"≈ 30 VDC (21-32 V)","max_current":"640 mA per PSU"} |
Where to start
How many DALI devices are offline?
Full guided diagnosis in the app
The diagnostic tree for this fault has 7 guided steps with measurements, checks and resolutions. You'll find it in BASIQ, one of the five IndexOS apps: free, works offline.
Printable sheet + Siemens updates
Leave your email: get the link to the printable Siemens error-code sheet and a heads-up when we add new codes and guides.
Double opt-in, zero spam, one-click unsubscribe.
The same fault on other brands
More Siemens codes
- 0xE900 / 0xE901 — IO-Link communication lost (device not responding)
- 16#0001 / Power Dropout — Unstable PLC power supply — cyclic restarts
- 16#0006 (OB82 DI) — Digital input module — input not reading (stuck at 0)
- 16#2942 — PLC Communication Fault / Network Timeout
- 32767 / -32768 (Overflow/Underflow) — Analog input module — full-scale reading or error
- ANSI 50/51 — Overcurrent Protection 50/51 Trip
- COMM LOSS — Supervision Network Loss
- DAMPER FAULT — Smoke Damper / Extraction Failure