Alarm 13 Danfoss — Overcurrent Fault

At a glance

Severity
FAULT STOP
Domain
DRIVES
Reference standard
IEC 61800-5-1
Product / context
Overcurrent

What it means

Overcurrent detected during acceleration or at steady state. The drive detects an output current exceeding the maximum allowed threshold and immediately trips to protect the IGBT power module. Can be caused by a short circuit on the motor cable, mechanical load blockage, incorrect ramp time settings, or drive undersizing relative to the motor.

Probable causes

Where to start

Disconnect the motor cable from the drive U/V/W terminals and measure the insulation between phases and to ground with a 500V megger. Are the values above 1 MΩ?

Full guided diagnosis in the app

The diagnostic tree for this fault has 7 guided steps with measurements, checks and resolutions. You'll find it in ElectraIQ, one of the five IndexOS apps: free, works offline.