CE Bosch Junkers — Low Water Pressure / Pressure Switch Open
At a glance
- Severity
- FAULT STOP
- Domain
- HEATING_SYSTEM
- Reference standard
- EN 15502 / DPR 74/2013
- Product / context
- Heating circuit pressure too low
What it means
System water pressure below the minimum safety threshold.
Probable causes
- Water leak in the system (radiators, fittings, valves)
- Expansion vessel discharged or membrane ruptured
- Water pressure switch faulty or badly calibrated
- Filling valve closed
Reference values
| system pressure bar | {"cold_optimal":"1.0-1.5","min_operating":"0.8","safety_valve":"3.0","expansion_vessel":"1.0-1.5 bar precharge (matching cold pressure)"} |
|---|
Where to start
Is the gauge pressure below 0.8 bar?
Full guided diagnosis in the app
The diagnostic tree for this fault has 7 guided steps with measurements, checks and resolutions. You'll find it in HVACIQ, one of the five IndexOS apps: free, works offline.